• Kentec KA11040M2 Fire Control Panels

    • 2 wire systems, reduces installation cabling
    • 2-wire repeaters and ancillary boards via serial bus
    • Fully programmable using simple menu options
    • Adjustable sounder delay time
    • Sounder configuration options
    • Zonal sounder delay for detectors only
    • Zonal sounder delay for call points only
    • Coincidence output via ancillary board
    • Short circuit fire selectable by zone
    • Non latching selection by zone
    • Silent zones (common sounder outputs)
    • 0.075Amp Standby
    • 385 x 310x 90mm
    • 3 year warranty
    • Kentec KA11040M2 Fire Control Panels data sheet
  • Kentec T11020M2 Fire Control Panels

    • Construction : 1.2 mm mild sheet steel
    • Finish : Epoxy powder coated
    • Colour – lid & box : BS 00 A 05 grey – fine texture
    • Colour – control plate & labels : RAL 7047 light grey – satin
    • Supply voltage : 230 VAC (+10%/-15%)
    • Mains supply fuse : 1.6 A 250V
    • Power supply DC rating : 24V 3A
    • Maximum battery size : 7Ah 12V (2 per panel)
    • Fault contact rating : 30 VDC 1A
    • Local fire contact rating : 30 VDC 1A
    • Fire contact rating : 30 VDC 1A
    • Sounder output rating : 0.5A per output (Max 1.6A over all outputs)
    • Detection zone current : 1.6 mA
    • Detection zone EOL resistor : 6K8 5%
    • Active EOL : K14606K (optional)
    • Sounder output EOL resistor : 10K 5%
    • Cable capacity : 2.5 mm©
    • Operating temperature : -5°C a +50°C
    • Operating humidity : < 95% (non condensing)
    • Dimension : 385 mm x 310 mm x 90 mm
    • Standby current 2 zones : 0.065 A
    • Standby current 4 zones : 0.075 A
    • Standby current 8 zones : 0.093 A
    • Alarm current 2 zones : 0.15 A
    • Alarm current 4 zones : 0.30 A
    • Alarm current 8 zones : 0.63 A
    • 3 year warranty
    • Kentec T11020M2 Fire Control Panels user manuals
    • Kentec T11020M2 Fire Control Panels data sheet
  • C-Tec XFP501E/X Fire Control Panels

    • Apollo Xp95/Discovery Protocol
    • Keypad/keyswitch entry
    • 1.4A psu
    • Third-party certified to EN54-2/4 by the Loss Prevention Certification Board (LPCB).
    • Compatibility with Apollo’s XP95/Discovery protocol.
    • Two independently programmable conventional sounder circuits.
    • Two programmable inputs.
    • A fault output relay and three programmable relay outputs with voltage free changeover contacts.
    • A selection of zone dependency/coincidence functions.
    • A day/night (building occupied/unoccupied) function.
    • An investigation delay period function.
    • Phased evacuation facility.
    • An alarm counter that records how many times the panel has been in alarm state.
    • Powerful short circuit protected loop drivers, capable of supporting up to 40 loop powered 10mA sounders per loop.
    • An integral EN54-4/A2 switch mode power supply.
    • Adjustable contamination levels.
    • Earth fault monitoring.
    • Combined keypad / keyswitch entry to Access Levels 2 and 3.
    • 999 event monitoring.
    • An intuitive Windows based upload-download PC program.
    • Up to eight XFP main panels (any variant) can be connected onto a two-wire RS485 non-redundant network. Alternatively, up to eight XFP repeaters can be connected to any non-networked main panel.
    • Plastic enclosure
    • 1 year warranty
    • instruction 
    • start guide 
    • C-Tec XFP501E/X Fire Control Panels user manual 
    • C-Tec XFP501E/X Fire Control Panels data sheet
  • Kentec KA11020M2 Fire Control Panels

    • Construction 1.2mm mild sheet steel
    • IP Rating IP30
    • Finish Epoxy powder coated
    • Colour – lid & box BS 00 A 05 grey – fine texture
    • Colour – control panel & labels RAL 7047 light grey – satin
    • Weight 6kg
    • Supply Voltage 230V AC (+10%/-15%)
    • Mains supply fuse 1.6 Amp 250V
    • Power supply DC rating 24V 3 Amps
    • Maximum battery size 7Ah 12V (2 per panel)
    • Fault contract rating 30V DC 1 Amp
    • Local fire contract rating 30V DC 1 Amp
    • Fire contract rating 30V DC 1 Amp
    • Common Sounder output rating 0.5A per output (max 1.6A over all outputs)
    • AlarmSense Sounder output rating 0.2A per output
    • Detection zone current 1.6 milliamps
    • zone EOL resistor 3K3 5%
    • Sounder output EOL resistor 10k 5%
    • Cable capacity 2.5mm² per terminal
    • Operating temperature -5°C to +40°C
    • Operating humidity <95% (non condensing)
    • 3 year warranty
    • Kentec KA11020M2 Fire Control Panels data sheet